Warning: fopen(/home/faraadaycom/public_html/system/storage/cache/cache.catalog.language.1711671502): failed to open stream: Disk quota exceeded in /home/faraadaycom/public_html/system/library/cache/file.php on line 49Warning: flock() expects parameter 1 to be resource, bool given in /home/faraadaycom/public_html/system/library/cache/file.php on line 51Warning: fwrite() expects parameter 1 to be resource, bool given in /home/faraadaycom/public_html/system/library/cache/file.php on line 53Warning: fflush() expects parameter 1 to be resource, bool given in /home/faraadaycom/public_html/system/library/cache/file.php on line 55Warning: flock() expects parameter 1 to be resource, bool given in /home/faraadaycom/public_html/system/library/cache/file.php on line 57Warning: fclose() expects parameter 1 to be resource, bool given in /home/faraadaycom/public_html/system/library/cache/file.php on line 59Warning: Cannot modify header information - headers already sent by (output started at /home/faraadaycom/public_html/system/framework.php:42) in /home/faraadaycom/public_html/catalog/controller/startup/startup.php on line 96Warning: fopen(/home/faraadaycom/public_html/system/storage/cache/cache.currency.1711671502): failed to open stream: Disk quota exceeded in /home/faraadaycom/public_html/system/library/cache/file.php on line 49Warning: flock() expects parameter 1 to be resource, bool given in /home/faraadaycom/public_html/system/library/cache/file.php on line 51Warning: fwrite() expects parameter 1 to be resource, bool given in /home/faraadaycom/public_html/system/library/cache/file.php on line 53Warning: fflush() expects parameter 1 to be resource, bool given in /home/faraadaycom/public_html/system/library/cache/file.php on line 55Warning: flock() expects parameter 1 to be resource, bool given in /home/faraadaycom/public_html/system/library/cache/file.php on line 57Warning: fclose() expects parameter 1 to be resource, bool given in /home/faraadaycom/public_html/system/library/cache/file.php on line 59Warning: Cannot modify header information - headers already sent by (output started at /home/faraadaycom/public_html/system/framework.php:42) in /home/faraadaycom/public_html/catalog/controller/startup/startup.php on line 154 General-UPS-PowerSupply(12V 3A RelayAlarm)

General UPS PowerSupply (12V 3A RelayAlarm)

Rs.2,445.00
Product Code: PowerSupply FPS 1203N-01BR
Availability: In Stock
Technical Parameter:

Model No.: FPS1203N-01BR

· Uninterruptible PSU
· Relay Alarm

· Metal Case With Key-lock

· 85% High efficiency

· 2 Years Warranty

· Full Protection
· No delay battery boot up
· 100% full load burn-it test

· Work with different optional modules

FPS 1203N-01BR is an UPS power supply, its main output is 13.6V / 3A, while it also provides maximum 1A charge current. It could be used for CCTV surveillance / access control / fire alarm and other security systems.


INPUT

Voltage Range

190 - 240VAC

Frequency Range

50 - 60Hz

OUTPUT

Voltage (AC Mode)

13.6V ±2%

Voltage (Battery Mode)

Same as battery voltage

Rated Current

3A

Rated Power (Max.)

54.4W (with 1A charge current)

Efficiency (Typ.)

>85%

Ripple & Noise

<120mVp-p

Output Channel

1 channel

CHARGING

Voltage

13.6V ±2%

Current

1A (max.)

Constant voltage mode, charge current decreases when battery voltage increases.

PROTECTION

Input

2A / 250VAC fuse

Overload

3.9A ±5%

Hiccup mode, recovers automatically after fault condition is removed.

Over Voltage

16V ±5%

Hiccup mode, recovers automatically after fault condition is removed.

Battery Low Voltage

10V ±2%

PSU shuts down until AC power recovers.

Short Circuit

Hiccup mode, recovers automatically after fault condition is removed.

ENVIRONMENT

Temperature

Working: -20 - 50

Storage: -30 - 80

Humidity

Working: 20 - 80%RH

Storage: 10 - 90%RH

LED INDICATOR

Red

On

AC power is on

Green

On

DC output is on

Yellow

Off

Battery is fully charged or no battery

Flickering

Battery is charging

SAFETY & EMC

EMC Standards

EN 55022: 2010, EN 55024: 2010, EN 61000-3-2: 2014, EN 61000-3-3: 2013

LVD Standards

EN 60950-1: 2006 + A11: 2009 + A1: 2010 + A12: 2011 + A2: 2013

METAL BOX & PACKING

Default Metal Box

203 x 163 x 74mm, fits for 1 pc 12V 9Ah battery.

Optional Metal Box

265 x 195 x 75mm, fits for 1 pc 12V 10Ah battery.

295 x 195 x 90mm, fits for 1 pc 12V 20Ah battery.

Packing

41 x 35 x 23.5cm / CTN, 11.5kg / CTN, 10pcs / CTN (default metal box)